Technical details
The ESE 275 TIA diesel generator produced by Endress Group Romania under the Zenessis brand is equipped with IVECO Stage III C87TE3F engine, Marelli MXB-E 250 MB4 / Strathon ECO 275 KW alternator and ComAp INTELILITE AMF 25 control system, which ensures the generator start up and parameter control, in manual or automatic system. The generator can be supplied with remote control and monitoring as well as other options. Zenessis power generators are guaranteed for 36 months, up to 2000 operating hours.
Standard features
Command & control panel with measurement & metal control devices, protection class IP54 |
Static battery charger |
Dynamic battery charging alternator |
Controlled thermostat heater for coolant |
Oversized start battery |
Emergency stop button |
Chassis with fuel tank sized for 8hrs of autonomy |
Vibration dampers |
Fuel level measuring device |
Electrical lines protected with tubing & gland |
Residential silencer |
Access doors on all 4 sides provided with locks |
Crane or forklift handling system |
Flameproof and soundproof insulation |
Protective pads |
Metal hinges |
Iveco diesel engine
Engine
Model | IVECO Stage III |
Model | C87TE3F |
No. of cilinders & arrangement | 6 in linie |
Cooling system | Water cooling |
Displacement (l) | 8,7 I |
Injection system | Direct with turbine |
Standby power (kWm) | 256 KWh |
Speed (rpm) | 1500 rpm |
Bore & Stroke (mm) | 117 x 135 mm |
Compression factor | 17,5:1 |
Regulator | Electronic |
Total oil capacity (l) | 28 I |
Engine coolant & radiator capacity | 63 l |
Fuel consumption at 100% prime load | 59 l / h |
Standard features
Alternator Marelli / Strathon
Model | MXB-E 250 MB4 / ECO 275 KW |
Frequency (Hz) | 50 Hz |
Concept | Brushless, 4 poles |
Phases | 3 |
Voltage (V) | 400 / 230 V |
Protection class | H |
Excitation system | Electronic |
Performance | 93% |
Protection | IP23 |
Certification test | test EN 10204:2001 |
Control panel
Made in metal box, IP54 degree, with lock. The control panel is equipped with the ComAp AMF25 control module, with the possibility of starting and stopping the generator, both in automatic and in electric mode. The control panel monitors the power grid and can command and control the ATS panel (automatic transfer switch).
Control panel standard specifications :
The command and control panel is mounted inside the casing, in a metal box with IP 54, equipped with a viewing glass, equipped with:
ComAp AMF 25 command module |
Static battery charger |
Emergency stop button & circuit breaker fuses control |
Overcurrent differential protection |
Protection relays |
Control panel
1. Left button |
2. Right button |
3. Horn Reset button |
4. Fault Reset button |
5. Up button |
6. Page button |
7. 7. Down button |
8. Enter button |
9. Start button |
10. Stop button |
11. GCB button. Works in MAN and TEST modes only 12. MCB button. Works in MAN and TEST modes only |
12. MCB button. 12. MCB button. Works in MAN and TEST modes only |
13. Generator status indicator |
14. GCB On. Green LEDs are on if GCB is closed and Gen-set is healthy |
15. Load |
16. Graphic B/W display, 132 x 64 pixeli |
17. Mains status indicator |
18. MCB On. Green LEDs are on if MCB is closed and Mains is healthy |
Configuration
Microprocessor control |
132 x 64 pixeli LCD display |
Programming on front panel as well as through PC software |
Control buttons and soft touch navigation |
Remote communication via USB or with optional modules via RS232, RS485, Ethernet or SMS |
Store 180 events with date and time |
Maintenance programming 3 levels |
Engine heater control –Optional |
Command module standard specifications:
Configuration
1. ComAp AMF25 command module |
2. Circuit Breaker protection |
3. Locks |
4. Alarm |
5. START button ON / OFF |
6. Hinges |
7. Maintenance schedule |
8. Metal box |
Displays:
Engine – engine speed; oil pressure; coolant temperature; running time; battery voltage; maintenance data. |
Alternator – voltage (L – L, L – N); current (L1 – L2 – L3); frequency; kW; Pf; kVAr; kWh,kVAh, kVarh; phase sequence. |
Main network – voltage (L – L, L – N); frequency, mains ready; mains off; generator set ready, generator set disconnected, active power kW, apparent power kVA, reactive power kVA r, power factor, phase sequence. |
Warning – battery faulty charging, low battery voltage, fail to stop, low fuel level, overload, phase reversing, speed sensor failure. |
Alarms – low oil pressure, high engine temperature, under / over voltage, under / overfrequency, under / overvoltage, ECU fault -optional. |
Status displays – missed start, emergency stop, low oil pressure, high engine temperature, under / overspeed, under / overfrequency, under / overvoltage, oil sensor, phase rotation, overload, overcurrent group, phase reversal. |
Static battery charger:
Made with TSD technology, with high efficiency. Protected for short- circuit currents, it can be used as a current source, input voltage 196-264 V, output voltage 27.6 V / 5A or 13.8 V / 5A.
Standards
Electrical safety / EMC, BS EN 60950; BS EN 60950 – 6 – 2 EMC; BS EN 61000 – 6 – 4 EMC.
Housing
Made of galvanized steel, painted in electrostatic field, soundproofed. It is modularly designed with in-door access doors on all sides of the generator. The exhaust pan is residential type, mounted inside the casing. The housing are designed to optimize the cooling of the engine and alternator assembly, and can be mounted outdoors, providing protection against weathering and low noise levels.
Housing
1. Command module |
2. View window |
3. Access door for control module |
4. Points for crane lifting (optional) |
5. Spaces for handling with the forklift |
6. Engine and alternator access door |
7. Air intake grills |
8. Handles provided with locks |
9. Fuel supply bus (optional) |
10. „Sleigh chassis” fitted with lifting/pulling holes |
11. Emergency button |
12. Exhaust Gas Valve |
13. Cable access space |
14. Hot air outlet grills |
15. Protective pads |
Dimensions and weight
Dimensions and weight of open genset
Sizes (length x width x height) (mm) | 3500 x 1262 x 1670 |
Weight (kg) | 2100 |
Fuel tank capacity (liters) | 500 |
Dimensions and weight of the closed genset
Sizes (length x width x height) (mm) | 3500 x 1262 x 2000 |
Weight (kg) | 3200 |
Fuel tank capacity (liters) | 500 |
Optional features
Electrical panel anti-condensation heating system |
Fuel / oil heating system |
Coolant heating circulation pump |
Oil drain pump |
Remote monitoring & control system |
ATS load transfer panel, 4 poles |
Differential protection wit 4 poles |
Sokets 400 V/ 230 V |
Fuel filter with water detection |
Bypass panel – ENDRESS patented invention – OSIM patent 00010 / 2012 |
Trailer |
Start by remote control |
Groundless protection |
Interior lightings with switches operated at doors opening |
Liquid retention tray |
Liquid leakage detection sensor |
Motorized ATS, ENDRESS patented invention – OSIM patent 00048 / 2015 |
Exterior fuel filler cap with lock |
Pocket system integrated in the chassis for lifting with forklift |
Fire extinguisher with internal housing support |
Super soundproof housing |
Intake air heating spark plug |
Grounding electrodes |
Fuel transfer automatic pump |
Mobile distribution panel with 4 sockets |
Cable reel |
Fire detector with automatic shutdown generator set |
Fire extinguishing system with inert gas |
Optional: RAR approved auto trailer
Model: EGR 3500
Endress Group Romania S.R.L. certifications:
ISO 9001 : 2008, ISO 14001 : 2005, ISO 18001 : 2008.
ZENESSIS generators are CE compliant, and are tested according to the EU legislation on noise levels 2000 / 14 / EC.
Reference ambient conditions: 1000 mbar; 25° C; 30% relative humidity; power according to ISO 3046 / ISO 8528 standards
Prime power (PRP) – ISO 8528
Primary power (PRP) – is the continuous power that a generator is capable of supplying continuously while supplying a variable electrical load when operating for an unlimited number of hours per year under agreed operating conditions, within the maintenance intervals and procedures prescribed by the manufacturer.
Standby power (ESP) – ISO 8528
Standby power (ESP) is the maximum power available at a variable load, under the operating conditions provided, that a generator is able to provide in case of power failure or under test conditions, maintenance intervals and procedures being performed as prescribed by the manufacturer.