ZRM 3 ZCR

Engine manufacturer
Zenessis
Fuel
electric
Amperage
N/A
Power (kVA)
3
Power (kW)
N/A
Request quote
Series Power KVA Amperage Engine manufacturer Power KW
ZNG 1010N/AZenessis10
ZNG 1515N/AZenessis15
ZNG 4040N/AZenessis40
ZRT 120N/AN/AZenessis
ZMT 20N/AN/AZenessisN/A
ZMT 10N/AN/AZenessisN/A
ZRM 1010N/AZenessis10
ZRM 6N/AN/AZenessis
ZRM 3N/AN/AZenessis
ZRM 2N/AN/AZenessis120
ZC 3K5N/AZenessis5
ZRM 3 ZCR3N/AZenessisN/A
ZC 5KN/AN/AZenessis5
ZRM 1 STN/AN/AZenessis120
ZRM 1N/AN/AZenessis120

Technical specifications

Input voltage.230 VAC
Input frequency50/60 Hz
Power (kVA)3
Input power factor>0,99
Output efficiencyMore than 93%
TechnologyTRUE ON LINE Double conversion
ClassificationVFI-SS-111 (EN 62040-3)
Power range3 kVA
Number of phases1:1
ModelZRM 3 ZCR
Power3000 VA / 2700 W
Number of input : output phases 1:1

Entry

Voltage (V)230 VAC
Tension beach160 – 290 VAC
Frequency (Hz)50-60 Hz ± 3Hz (automatic detection)
THDi<3%
Input power factor.≥0,99
Connections1 x IEC 320 C20

Exit

Voltage (V)230 V
Output power factor0,9
Static/dynamic voltage regulation±1% / ±3%
Frequency (Hz)50/60 Hz ± 3 Hz (automatic detection)
Overload capacity110% – no limit, 130% – 5 min., 140% – 30 sec., >140% – 1,5 sec.
Performance>97%
Shape of the lineSinusoidala
Type and number of sockets8 x IEC320-C13 ,1 x IEC320-C19 internal, battery powered
Transfer time0 ms
Creast factor3:1

Batteries

ModelSigilate plumb-acid
Cold startyes
Connector for external batteriesyes
Loading timeMaximum 6 hours
Autonomy10 min (100% load), 3 min (50% load)

Weight and dimensions

UPS dimensions and weight (W x D x H)438 x 630 x 88 (2U)
Weight ( Kg)29,3 kg

Communications

Operation indicatorLCD + LED indicators, audible alarm
CommunicationsStandard: USB, RS232, RJ – 45, Smart Slot, EPO
Optiuni: Dry Contact, card SNMP

Ambient

Noise level<45 dB
Operating temperature for UPS0°C ÷ 40°C
Recommended operating temperature for UPS15°C ÷ 25°C
Storage temperature-25°C ÷ 55°C
Humidity0 ÷ 95% (non-condensing)

Certification test

StandardsEN 62040-2:2005, EN 62040-2:2006
SafetyIEC62040-1-1, CE, 62040-3 :2001

Options

SNMP cards
Ambient sensor (EMD)
Bypass maintenance
REPO
Drycontact (AS-400)
Ekstra batteritilstand
Kit on 19″ saddle

Fill in the offer request: