zrt-removebg-preview

ZRT 120

Engine manufacturer
Zenessis
Fuel
electric
Amperage
N/A
Power (kVA)
N/A
Power (kW)
Request quote
Series Power KVA Amperage Engine manufacturer Power KW
ZNG 1010N/AZenessis10
ZNG 1515N/AZenessis15
ZNG 4040N/AZenessis40
ZRT 120N/AN/AZenessis
ZMT 20N/AN/AZenessisN/A
ZMT 10N/AN/AZenessisN/A
ZRM 1010N/AZenessis10
ZRM 6N/AN/AZenessis
ZRM 3N/AN/AZenessis
ZRM 2N/AN/AZenessis120
ZC 3K5N/AZenessis5
ZRM 3 ZCR3N/AZenessisN/A
ZC 5KN/AN/AZenessis5
ZRM 1 STN/AN/AZenessis120
ZRM 1N/AN/AZenessis120

Technical specifications

Input voltage380/400/415 VAC
Input frequency50/60 Hz
UPS operating temperatures0°C ÷ 40°C
Input power factor>0,99
ModelZRT 120 MODULAR SYSTEM
Powerfrom 30 / 27 to 120 / 108
Number of input : output phases 3:3
TopologyTrue On Line Double Conversion, Rectifier and Inverter with IGBT Technology, Transformerless SPWM Controlled

Entry

Voltage (V)380 / 400 / 415 VAC
Tension beach-40% ÷ +25 %
Frequency (Hz)50/60 Hz Range
Frequency range-20% ÷ +20 %
THDi<3%
Input power factor≥0,99

Exit

Voltage (V)380 / 400 / 415 VAC
Static/dynamic voltage regulation±0.5% / ±2%
Frequency (Hz)50/60 Hz ±0,05 Hz
Overload capacity (Inverter, pf=0.9)110% – 60 min., 125% – 10 min., 150% – 60 sec., >150% – 200msec.
Short circuit resistance340% of V nom for 200 msec.
Efficiency>96%
Linear THDu<0.5%
Non-linear THDu<1%
Efficiency in ECO MODE99%
Creast factor3:1

Batteries

ModelMaintenance-free, sealed VRLA AGM
Starting on batteriesyes
Configuration36 / 38 / 40 / 42 / 44 pcs.
Loading3 – 8 hours up to 90% of capacity according to DIN 41773

Weight and dimensions

UPS dimensions (W x D x H)600 x 1400 x 980 mm
UPS dimensions 120 kVA250 kg

Communications

Indicators operating modeLCD touch display, LED indicators, audible alarm
CommunicationsRS-232, RS-485, Potential free contacts, SNMP slot, MODBUS RTU/ASCII,
REPO, parallel connector, generator interface

Ambient

Noise level-dependent on load and temperature<50 dB (A)
Operating temperature for UPS0°C ÷ 40°C
Recommended operating temperature for UPS15°C ÷ 25°C
Storage temperature– 20 °C ÷ 40 °C
Humidity0 ÷ 95% (non-condensing)

Certification test

StandardsEC, EN 62040-2:2006 (EMC), EN 62040-1:2008 (LVD)

Options

SNMP web
Ambient sensor (EMD)
Battery compensation kit
REPO – Emergency button
BYpass external maintenance
External battery cabinets

Fill in the offer request: