Fuel consumption at 100 % prime load (kg/hr) NG/LP
28/23
Alternator
Alternator
Model
MXB-E 225 SB4 or ECO 110 KW
Frequency (Hz)
50 Hz
Concept
Brushless, 4 poles
Phases
3 + n
Voltage (V)
400 / 230
Insulation class
H
Excitation system
Electronic
Performance
93%
Protection
IP23
Test Certification
EN 10204 : 2001
COMMAND PANEL
Made in metal box, IP54 degree, with lock. The control panel is equipped with the control ComAp AMF25, equipped with the possibility of starting and stopping the generating set, both in automatic mode and in electric module. The control module monitors the power grid and can command and control the AAR panel (automatic reserve release).
Control panel
1. Left button
2. Right button
3. Horn Reset button
4. Fault Reset button
5. Up button
6. Page button
7. Down button
8. Enter button
9. Start button
10. Stop button
11. GCB button. Works in MAN and TEST modes only 12. MCB button. Works in MAN and TEST modes only
12. MCB button. 12. MCB button. Works in MAN and TEST modes only
13. Generator status indicator
14. GCB On. Green LEDs are on if GCB is closed and Gen-set is healthy
15. Load
16. Graphic B/W display, 132 x 64 pixeli
17. Mains status indicator
18. MCB On. The green LEDs are “on” when the MCB is closed and the network is within the preset parameters.
◆ Standard control panel specifications: The command and control panel is mounted inside the enclosure, in a metal box with IP 54, provided with glass. for viewing, equipped with:
Control panel
ComAp AMF 25 command module
Static battery charger
Emergency stop button & circuit breaker fuses circuit control
Overcurrent differential protection
Protection relays
Configuration:
1. ComAp AMF25 command module
2. Circuit Breaker protection
3. Locks
4. Alarm
5. START button ON / OFF
6. Hinges
7. Maintenance schedule
8. Metal box
◆ Standard specifications of the control module:
Microprocessor control
132 x 64 pixeli LCD display
Programming on front panel as well as through PC software
Control buttons and soft touch navigation
Remote communication via USB or with optional modules via RS232, RS485, Ethernet or SMS
Store 180 events with date and time
Maintenance programming 3 levels
Engine heater control – optional
Displays: Engine: engine speed; oil pressure; coolant temperature; running time; battery voltage; maintenance date. Alternator: voltage (L – L, L – N); current (L1 – L2 – L3); frequency, active power kW, apparent power kVA, reactive power kVA r, power factor, phase sequence. Main network: voltage (L – L, L – N); frequency; prepared main network; uncoupled main network; prepared genset; uncoupled genset, , active power kW, apparent power kVA, reactive power kVA r, power factor, phase sequence.
Status displays: missed start, emergency stop, low oil pressure, high engine temperature, under/overload, under/overfrequency, under/overvoltage, oil fault sensor, phase rotation, overload, group overcurrent, phase reversal. ◆ Static battery charger: made with TSD technology, high efficiency. Protected for short- circuit currents, it can be used as a current source, input voltage 196-264 V, output voltage 27.6 V / 5A or 13.8 V / 5A. ◆ Standards: Electrical safety / EMC, BS EN 60950; BS EN 60950 – 6 – 2 EMC; BS EN 61000 – 6 – 4 EMC.
Housing
Made of galvanized steel, painted in electrostatic field, soundproofed. It is modularly designed with access doors inside on all sides of the generator. The exhaust pipe is a residential type, mounted in inside the housing. The housings are designed to optimise cooling of the engine and alternator assembly and can be fitted in outdoor, providing protection against the weather, and low noise. Painting is carried out with polyurethane paint with UV protection.
Housing
1. Command module
2. View window
3. Access door for control module
4. Points for crane lifting (optional)
5. Spaces for forklift handling
6. Engine and alternator access door
7. Air intake grills
8. Handles provided with locks
9. Sled type chassis equipped with eyelets
10. Damage button
11. Exhaust gas outlet flap
12. Cable access space
13. Hot air exhaust grille
14. Protective pads
Dimensions and Weight
Dimensions and weight of open genset
Sizes (length x width x height) (mm)
2690 x 1010 x 2000
Weight (kg)
1220
Ambient noise level (at 7 m distance)
82 db
Dimensions and weight of the closed genset
Sizes (length x width x height) (mm)
2890 x 1110 x 1700
Weight (kg)
1550
Ambient noise level (at 7 m distance)
70 db
Standard features
Control & command panel with metal measuring & control devices, IP 54 protection rating
Fire detector with automatic shutdown generator set
Endress Group Romania S.R.L. certifications:
ISO 9001 : 2008, ISO 14001 : 2005, ISO 18001 : 2008.
ZENESSIS generators are CE compliant, and are tested according to the EU legislation on noise levels 2000 / 14 / EC.
Reference ambient conditions: 1000 mbar; 25° C; 30% relative humidity; power according to ISO 3046 / ISO 8528 standards
Prime power (PRP) – ISO 8528
Primary power (PRP) – is the continuous power that a generator is capable of supplying continuously while supplying a variable electrical load when operating for an unlimited number of hours per year under agreed operating conditions, within the maintenance intervals and procedures prescribed by the manufacturer.
Standby power (ESP) – ISO 8528
Standby power (ESP) is the maximum power available at a variable load, under the operating conditions provided, that a generator is able to provide in case of power failure or under test conditions, maintenance intervals and procedures being performed as prescribed by the manufacturer.
Endress Zenessis Group manufactures power generators and UPS uninterruptible power supplies under the ZENESSIS brand!