grup electrogen generator de curent pe gaz PSI

Natural gas generator ESE 80 PSI

Engine manufacturer
Zenessis
Fuel
gas
Amperage
104.4
Power (kVA)
80 / 72
Power (kW)
64 / 58
Request quote

Engine

Engine

ModelPSI
Model6.7 L
No. of cylinders & arrangement6-in line
Injection systemDirect suction
Cooling systemWith liquid
Maximum standby power (kWm)59.86
Speed (rpm)1500
Cylinders (l)6.75
Inside diameter & stroke (mm)105 x 130
Compression factor 9,75 : 1
Regulator Electronic
Total oil capacity (l)14
Engine cooling agent capacity (l)16
Fuel consumption at 100 % prime load (kg/hr) NG/LP15,4/17

Alternator

Alternator

ModelMXB-E 225 XB4 or ECO 81 KW
Frequency (Hz)50 Hz
ConceptBrushless, 4 poles
Phases3 + n
Voltage (V)400 / 230
Insulation classH
Excitation systemElectronic
Performance93%
ProtectionIP23
Test CertificationEN 10204 : 2001

COMMAND PANEL

Made in metal box, IP54 degree, with lock. The control panel is equipped with the
control ComAp AMF25, equipped with the possibility of starting and stopping the generating set, both in automatic mode and in
electric module. The control module monitors the power grid and can command and control the AAR panel
(automatic reserve release).

Control panel

1. Left button
2. Right button
3. Horn Reset button
4. Fault Reset button
5. Up button
6. Page button
7. Down button
8. Enter button
9. Start button
10. Stop button
11. GCB button. Works in MAN and TEST modes only 12. MCB button. Works in MAN and TEST modes only
12. MCB button. 12. MCB button. Works in MAN and TEST modes only
13. Generator status indicator
14. GCB On. Green LEDs are on if GCB is closed and Gen-set is healthy
15. Load
16. Graphic B/W display, 132 x 64 pixeli
17. Mains status indicator
18. MCB On. The green LEDs are “on” when the MCB is closed and the network is within the preset parameters.

◆ Standard control panel specifications:
The command and control panel is mounted inside the enclosure, in a metal box with IP 54, provided with glass.
for viewing, equipped with:

Control panel

ComAp AMF 25 command module
Static battery charger
Emergency stop button & circuit breaker fuses circuit control
Overcurrent differential protection
Protection relays
Configuration:
1. ComAp AMF25 command module
2. Circuit Breaker protection
3. Locks
4. Alarm
5. START button ON / OFF
6. Hinges
7. Maintenance schedule
8. Metal box

◆ Standard specifications of the control module:

  • Microprocessor control
  • 132 x 64 pixeli LCD display
  • Programming on front panel as well as through PC software
  • Control buttons and soft touch navigation
  • Remote communication via USB or with optional modules via RS232, RS485, Ethernet or SMS
  • Store 180 events with date and time
  • Maintenance programming 3 levels
  • Engine heater control – optional
  • Displays:
    Engine: engine speed; oil pressure; coolant temperature; running time; battery voltage; maintenance date.
    Alternator: voltage (L – L, L – N); current (L1 – L2 – L3); frequency, active power kW, apparent power kVA, reactive power kVA r, power factor, phase sequence.
    Main network: voltage (L – L, L – N); frequency; prepared main network; uncoupled main network; prepared genset; uncoupled genset, , active power kW, apparent power kVA, reactive power kVA r, power factor, phase sequence.
  • Warnings:defective battery charging, low battery voltage, failed shutdown, overload, phase reversal, speed sensor fault.
  • Alarms: low oil pressure, high engine temperature, under/over temperature, under/overfrequency, under/overvoltage, ECU fault-optional.
  • Status displays: missed start, emergency stop, low oil pressure, high engine temperature, under/overload, under/overfrequency, under/overvoltage, oil fault sensor, phase rotation, overload, group overcurrent, phase reversal.
    ◆ Static battery charger: made with TSD technology, high efficiency. Protected for short- circuit currents, it can be used as a current source, input voltage 196-264 V, output voltage 27.6 V / 5A or 13.8 V / 5A.
    ◆ Standards:
    Electrical safety / EMC, BS EN 60950; BS EN 60950 – 6 – 2 EMC; BS EN 61000 – 6 – 4 EMC.

Housing

Made of galvanized steel, painted in electrostatic field, soundproofed. It is modularly designed with
access doors inside on all sides of the generator. The exhaust pipe is a residential type, mounted in
inside the housing.
The housings are designed to optimise cooling of the engine and alternator assembly and can be fitted in
outdoor, providing protection against the weather, and low noise. Painting is carried out
with polyurethane paint with UV protection.

Housing

1. Command module
2. View window
3. Access door for control module
4. Points for crane lifting (optional)
5. Spaces for forklift handling
6. Engine and alternator access door
7. Air intake grills
8. Handles provided with locks
9. Sled type chassis equipped with eyelets
10. Damage button
11. Exhaust gas outlet flap
12. Cable access space
13. Hot air exhaust grille
14. Protective pads

Dimensions and Weight

Dimensions and weight of open genset

Sizes (length x width x height) (mm)2300 x 1010 x 2000
Weight (kg)1100
Ambient noise level (at 7 m distance)82 db

Dimensions and weight of the closed genset

Sizes (length x width x height) (mm)2690 x 1110 x 1700
Weight (kg)1300
Ambient noise level (at 7 m distance)70 db

Standard features

Control & command panel with metal measuring & control devices, IP 54 protection rating
Static battery charger
Dynamic alternator charging batteries ori
Controlled thermostat heater for coolant
Oversized start battery
Emergency stop button
Flameproof and soundproof insulation
Vibration dampers
Residential silencer
Electrical lines protected with tubing & gland
Protective pads
Metal hinges
Access doors with locks
Crane or forklift handling system

Optional features

Anti-condensation heating system. electrical panels
Oil heating system
Coolant heating circulation pump
Oil drain pump
Motorized ATS, ENDRESS patented invention – OSIM patent 00048 / 2015
AAR transfer panel with 3/4 poles
3/4 pole differential protection
Sokets 400 V/ 230 V
Liquid retention tray
Liquid leakage detection sensor
Remote monitoring & control system
Intake air heating spark plug
Forklift pocket system integrated in the chassis
Fire extinguisher with internal housing support
Super soundproof housing
Interior lightings with switches operated at doors opening
Bypass panel – ENDRESS patented invention – OSIM patent 00010 / 2012
Trailer
Start by remote control
Groundless protection
Grounding electrodes
Fire extinguishing system with inert gas
Mobile distribution panel with 4 sockets
Cable reel
Fire detector with automatic shutdown generator set

Endress Group Romania S.R.L. certifications:

ISO 9001 : 2008, ISO 14001 : 2005, ISO 18001 : 2008.

ZENESSIS generators are CE compliant, and are tested according to the EU legislation on noise levels 2000 / 14 / EC.

Reference ambient conditions: 1000 mbar; 25° C; 30% relative humidity; power according to ISO 3046 / ISO 8528 standards

Prime power (PRP) – ISO 8528

Primary power (PRP) – is the continuous power that a generator is capable of supplying continuously while supplying a variable electrical load when operating for an unlimited number of hours per year under agreed operating conditions, within the maintenance intervals and procedures prescribed by the manufacturer.

Standby power (ESP) – ISO 8528

Standby power (ESP) is the maximum power available at a variable load, under the operating conditions provided, that a generator is able to provide in case of power failure or under test conditions, maintenance intervals and procedures being performed as prescribed by the manufacturer.

Fill in the offer request: