Technical specifications
Input frequency | 50/60 Hz |
Capacity (VA/W) | 10000 / 10000 |
UPS operating temperatures | 0°C ÷ 40°C |
Input power factor | >0,99 |
Model | ZRM 10 |
Power | 6000 VA/ 6000 W |
Number of input : output phases | 1:1 |
Entry
Voltage (V) | 208 / 220 / 230 / 240 VAC |
Tension beach | -30% ÷ +30% @ 100% ≥ load. ≥ 80% -40% ÷ +30% @ 80% ≥ load. ≥ 70% -48% ÷ +30% @ 70% ≥ load. ≥ 60% -52% ÷ +30% @ 60% ≥ load. ≥ 0% |
Frequency (Hz) | 50/60 Hz |
Tension beach | -20% ÷ +20% |
THDi | <3% |
Input power factor. | ≥0,99 |
Exit
Voltage (V) | 208/220/230/240 VAC |
Output power factor | 1,0 |
Static/dynamic voltage regulation | ±1% / ±3% |
Frequency (Hz) | 50/60 Hz ±0,05 Hz |
Overload capacity | 110% – 10 min, 130% – 1 min., >130% -1 sec. |
Randament On-line mode | >95% |
Eco mode yield | 99% |
Programming and controlling outlets | optional |
Terminal | n/a (Plug&Play) |
Creast factor | 3:1 |
Batteries
Cold start | yes |
Connector for external batteries | yes |
Loading time | 4 hours up to 90% of capacity (configurable) |
Weight and dimensions
UPS dimensions and weight (W x D x H) | 438 x 665 x 88 (2U); 17.0 kg I 20,0 kg |
Dimensions and weight of battery module (W x D x H) | 438 x 630 x 133 (3U); 63 kg |
Communications
Operation indicator | LCD + LED indicators, alarm |
Communications | Standard: USB, RS232, TVSS, Smart Slot, REPO Optional: Dry Contact, SNMP card |
Ambient
Noise level | <50 dB |
Operating temperature for UPS | 0°C ÷ 40°C |
Recommended operating temperature for UPS | 15°C ÷ 25°C |
Storage temperature | -25°C ÷ 55°C |
Humidity | 0 ÷ 95% (non-condensing) |
Certification test
Standards | EN 62040-2:2005, EN 62040-2:2006 |
Safety | IEC62040-1-1, CE, 62040-3 :2001 |
Options
SNMP cards |
Ambient sensor (EMD) |
Bypass maintenance |
EPO |
Drycontact (AS-400) |
Extra battery mode |
Rail kits 19″ |