Technical specifications
Input voltage | 380/400/415 VAC |
Input frequency | 50/60 Hz |
UPS operating temperatures | 0°C ÷ 40°C |
Power (kVA) | 40 |
Model | ZMZ 40K |
Power | 40 kW / 40 kVA |
Number of input : output phases | 3:3 |
Entry
Voltage (V) | 380 / 400 / 415 VAC |
Tension beach | 172÷287 Vac (L-N) / 300÷500 Vac (L-L) @ 100% sarc. 92÷287 Vac (L-N) / 160÷500 Vac (L-L) @ sarc. linear |
Frequency (Hz) | 50/60 Hz |
Frequency range | 20% ÷ +20% |
THDi | <3% |
Input power factor | ≥0,99 |
Exit
Voltage (V) | 380 / 400 /415 VAC |
Factor de putere | 1,0 |
Static/dynamic voltage regulation | ±1% / ±3% |
Frequency (Hz) | 50/60 Hz ±0,05 Hz |
Overload capacity | 105% – cont.; 115% – 60 min., 130% – 10 min., 150% – 60 sek., >151% – 0,2 sek. |
Efficiency in On-line mode | >96% |
Eco mode yield | 99% |
Creast factor | 3:1 |
Batteries
Model | Maintenance free, VRLA sealed |
Internal batteries | 2 x 36 x 9 Ah |
No. of batteries in string | Configurable: 30 ÷ 40 psc |
Maximum charging current | 20A |
Loading time | 3-8 hours at up to 90% capacity (configurable) |
Bypass
Automatic bypass | Bypass switch, uninterruptible switching |
Manual mechanical bypass | Standard |
Weight and dimensions
UPS dimensions and weight (L x W x H) | 450 x 840 x 967 mm / 160 kg |
Communications
Operating mode indicators | 4.3″ afisaj touch, LED indicators, sound alarms |
Communications | 3 x Smart Slot for additional communication cards, 2 x REPO (NO/NC), 3 x Free contacts, RS485, Modbus. |
Ambient
Noise level | <60 dB |
Operating temperature for UPS | 0°C ÷ 40°C |
Recommended operating temperature for UPS | 15°C ÷ 25°C |
Temperatura de depozitare | -20°C ÷ 55°C |
Humidity | 0 ÷ 95% (non-condensing) |
Standards
Resistance to interference | EN 62040-2:2005, EN 62040-2:2006 |
Safety | IEC62040-1-1, EC |
Options
Card SNMP |
RS 232 |
Bypass neintreruptibil extern |
Additional plate with free contacts |
Batteries in racks or modules |
Battery voltage compensation sensor |
Remote signalling panel |